Quick vessel sizing
Uses the current EMERY quick method unchanged. Enter known system volume or estimate at 12 L/kW.
Professional sealed-heating vessel sizing with quick and commercial-detail workflows. Calculation engine version EMERY-EV-QUICK-1.0.
Uses the current EMERY quick method unchanged. Enter known system volume or estimate at 12 L/kW.
Build actual system volume from boilers, components and measured pipework, or enter a known total.
This release changes deployment and iPad compatibility, not the current sizing method. Quick and Commercial modes use the same EMERY-EV-QUICK-1.0 acceptance-factor engine: expansion volume = system volume × expansion factor; final design pressure = PRV − 0.3 bar; acceptance factor = 1 − (Pi+1)/(Pf+1); vessel = expansion volume ÷ acceptance factor; then +10% heating reserve and round up. Manufacturer/project requirements take precedence. Water systems only; glycol/antifreeze requires fluid-specific data.